Back

HIGH

Eaton’s Cooper Power Series Form 6 Control and Idea/IdeaPlus Relays with Ethernet

Published Jul 20, 2015

Description

Eaton Cooper Power Systems ProView 4.0 and 5.0 before 5.0 11 on Form 6 controls and Idea and IdeaPLUS relays generates TCP initial sequence number (ISN) values linearly, which makes it easier for remote attackers to spoof TCP sessions by predicting an ISN value.

Affected products

Remediation

Vendor solution

Eaton’s Cooper Power Systems division has developed ProView 5.0 Revision 11 software that mitigates this vulnerability, and the Form 6 control version was released on June 12, 2015. Idea/IdeaPLUS relay ProView software versions began to be posted on June 30, 2015. ProView 5.0 Revision 11 will be compatible with any hardware and firmware Versions 5.0 and higher. Versions below 5.0 may be updated with the appropriate and corresponding hardware upgrades. Information on how to obtain and install these available remedies is available at:

http://www.cooperindustries.com/content/public/en/power_systems/resources/securitysupport.html

For additional technical information, please contact Eaton’s Cooper Power Systems at:

https://www.eaton.com/cybersecurity

Metrics

Weaknesses (2)

References (4)

Change history (0)

No recorded changes yet.

Sources
CVE.org / MITRE
Status PUBLISHED
Assigner icscert
Published Jul 20, 2015
Updated Sep 5, 2025
Reserved Dec 2, 2014
NVD
Status Modified
Modified Jun 17, 2026
Red Hat
Severity n/a
Public date n/a